3 modifying the setup using the setup dip switch, Run on power up (position 1) -5 – Rockwell Automation 1329I Integrated AC Drive/Motor, Series A User Manual
Page 39
Step 8 - Verify the Setup and Adjust Switches if Required
8-5
1329I-5.0 Integrated Drive/Motor — January, 1999
8.3
Modifying the Setup Using the Setup DIP Switch
The switches in the 10-position setup DIP switch define the characteristics of the 1329I
unit as shown in Figure 8.4. The switches are preset at the factory to suit a wide range
of applications and normally do not need to be changed. The following sections describe
how to modify the setup to suit your specific application, if required.
Important:
Changes to the DIP switch settings are recognized only while the drive is
stopped.
Figure 8.4
Setup DIP Switch Selections
8.3.1 Run On Power Up (Position 1)
On Standard Units only, enabling this feature causes output power to be applied to the
Motor Section automatically at drive power up.
Important:
If AC power is lost, the drive will restart if the Standard Unit is wired for
2-wire control.
Run On Power Up
Speed Reference
Relay Control Output
Auto Restart
Torque Curve
Stop
Reverse
Minimum Speed
Not Used
Not Used
Disabled
From Operator Controls
Running
Disabled
Variable
Coast-to-Rest
Enabled
3 Hz
Enabled
From Terminal Block
Faulted
Enabled
Constant
Ramp-to-Rest
Disabled (Reverse Lockout)
From Terminal Block
OFF
ON
OFF
ON
ATTENTION: When this feature is enabled, the drive may start at any
moment. This feature may only be used as outlined in NFPA79, Under
Voltage Protection for specialized applications. Equipment damage
and/or personal injury or loss of life may result if this feature is used in
an inappropriate application.