Terminals and wiring – Rockwell Automation 1606-XLS240UPSD Power Supply Reference Manual User Manual
Page 15
All parameters are specified at an input voltage of 24V, 10A output load, 25°C ambient and after a 5 minutes run-in time unless noted otherwise.
It is assumed that the input power source can deliver a sufficient output current.
Rockwell Automation Publication 1606-RM017A-EN-P — February 2014
15
Bulletin 1606 Switched Mode Power Supplies
15. Terminals and Wiring
12V Terminal
Signal terminals
Power terminals
(except 12V)
Type Bi-stable,
quick-connect
spring-clamp terminals.
Shipped in open position.
Lockable plug connector
with spring-clamp
terminals.
Plug connector with screw
terminal. Shipped in open
position. To meet GL
requirements, unused terminal
compartments should be closed.
Solid wire
0.5-6mm
2
2
2
0.1-2.5mm
0.2-1.5mm
2
2
2
Stranded wire
0.5-4mm
0.1-2.5mm
0.2-1.5mm
AWG 20-10AWG
28-12AWG
22-14AWG
Ferrules
Allowed, but not required
Allowed, but not required
Allowed, but not required
Pull-out force
10AWG:80N, 12AWG:60N, 14AWG:50N, 16AWG:40N
according to UL486E
Not applicable
Recom. screwdriver
Not required
3,5mm slotted
3,5mm slotted
Tightening torque
Not applicable
Not applicable
0.4Nm, 3.5lb.in
Wire stripping length
10mm / 0.4 in.
8.5mm / 0.34 in.
6mm / 0.24 in.
Fig. 15-1 Spring-clamp terminals, connecting a wire
1. Insert the wire
2. Close the lever
To disconnect wire:
reverse the procedure
Instructions:
a)
Use appropriate copper cables, that are designed
for an operating temperature of 60°C
b)
Follow national installation codes and regulations!
c)
Ensure that all strands of a stranded wire are properly
inserted in the terminal connection!
d)
Up to two stranded wires with the same cross section
are allowed in one connection point.