Commands, Related functions – Rockwell Automation 1408-EMxx PowerMonitor 1000 Unit User Manual
Page 68
![background image](/manuals/578619/68/background.png)
68 PowerMonitor 1000 Unit
Rockwell Automation Publication 1408-IN001E-EN-P - September 2013
Commands
The power monitor offers the following commands. The power monitor Commands table can
be accessed using the LCD screen, the HyperTerminal communication tool, the Web interface,
or via communication.
Commands that do not apply to the power monitor model are ignored.
Related Functions
•
Configuration lock
Command
Parameters
Action
Set kWh register
GWh / kWh forward
GWh / kWh reverse
Presets forward and reverse energy
values, resets if parameters = 0
Set kVARh register
GVARh / kVARh forward
GVARh / kVARh reverse
Set kVAh register
GVAh / kVAh forward
GVAh / kVAh reverse
Clear all energy registers
-
Resets all energy values
Set Status 1 count
New status 1 count
Presets or resets status input count
Set Status 2 count
New status 2 count
Clear energy log
-
Clears all data from energy log
Force KYZ output on
-
Forces the KYZ output state, over-rides
automatic action
Force KYZ output off
-
Remove force from KYZ
-
Restores automatic action of KYZ output
as configured
Restore factory defaults
-
Clears all user-configured values from the
setup menus to their factory default
settings
Reset system
-
Warm reboot: Performs a power-on self
test of the power monitor
Test wiring connections
-
Perform wiring diagnostics
Clear min/max records
Min/max record number
Clears selected min/max record or all
records if parameter = 0
Store and clear current load factor record -
Simulates end-of-month push of
in-process current month into the
monthly load factor record stack
Clear load factor log
Clears all load factor log records
Store and clear current TOU record
Simulates end-of-month push of
in-process current month into the
monthly TOU record stack
Clear TOU log
Clears all TOU log records
Clear error log
Clears the error log