Rockwell Automation 1408-EMxx PowerMonitor 1000 Unit User Manual
Page 41

PowerMonitor 1000 Unit 41
Rockwell Automation Publication 1408-IN001E-EN-P - September 2013
•
Waiting Command - five minutes have elapsed since the most recent command.
•
Out of Range - measured phase angles are outside the range of the selected system power
factor.
•
Voltage or current input missing (input below the metering threshold) or inverted
(reverse polarity, 180 degrees out of phase)
–
-1 — Test not run; see wiring status for reason.
–
0 — Pass, all inputs present / correct polarity.
–
1 — Phase 1 missing / inverted.
–
2 — Phase 2 missing / inverted.
–
3 — Phase 3 missing / inverted.
–
12 — Phase 1 and 2 missing / inverted.
–
13 — Phase 1 and 3 missing / inverted.
–
23 — Phase 2 and 3 missing / inverted.
–
123 — All 3 phases missing / inverted.
•
Voltage rotation
–
-1 — Test not run; see wiring status for reason.
–
123 — Forward phase rotation (ABC).
–
132 — Reverse phase rotation (ACB).
–
4 — Invalid phase rotation (2 inputs wired with same phase).
•
Current rotation, referenced to voltage Phase 1
–
-1 — Test not run; see wiring status for reason.
–
123 — Forward rotation (ABC).
–
231 — Forward rotation, 120 degrees displaced (BCA).
–
312 — Forward rotation, 240 degrees displaced (CAB).
–
132 — Reverse rotation (ACB).
–
213 — Reverse rotation, 120 degrees displaced (BAC).
–
321 — Reverse rotation, 240 degrees displaced (CBA).
–
4 — Invalid phase rotation (2 inputs wired with same phase).
Forward phase rotation is not required to pass wiring diagnostics. Before changing wiring
connections, refer to both the voltage / current rotation and voltage / current inverted status to
select the correct analog input.