Network Time Synchronization
Network time synchronization is available only on units equipped with the optional Ethernet
network. Set-up parameters are found in the Ethernet communication set-up menu. The power
monitor updates its time from a simple network time protocol (SNTP) server or an anycast
group of SNTP servers, depending on setup parameter values. Network-time synchronization
set-up parameters are found in the Ethernet communication set-up menu.
Related Functions
•
Demand metering
•
Data logging
Parameter
Description
Range
Default
User Setting
SNTP Mode
Select
0 = Disable
1 = Unicast – Specify the IP
address of a unicast SNTP server.
2 = Anycast mode – Specify the
broadcast IP address of a SNTP
anycast group.
0…2
0
SNTP Update
Interval
Defines how often the time is
updated from the SNTP server.
1…32766 minutes
300
Time Zone Select There are 32 available time zones.
0…32
7 (Eastern Time)
Time Server IP
Address
Unicast server or anycast group IP
address in format aaa.bbb.ccc.ddd.
0.0.0.0…
255.255.255.255
0.0.0.0