Configuration lock input – Rockwell Automation 1408-EMxx PowerMonitor 1000 Unit User Manual
Page 66

66 PowerMonitor 1000 Unit
Rockwell Automation Publication 1408-IN001E-EN-P - September 2013
Related Functions
•
Log status input changes
•
Configuration lock
Configuration Lock Input
Unauthorized changes to the power monitor setup are prevented when the configuration-lock
input terminals, CF and CF1, are connected together.
This feature applies to all models.
Operation
The following set-up parameters and commands are locked when the configuration lock is
applied:
•
Analog input setup menu: all parameters
•
Advanced setup menu
•
Metering result averaging
•
Log status input changes
•
KYZ setup
•
Status input 1 and 2 input scale
•
Demand setup
•
Ethernet communication set-up menu
•
Network demand setup
The following commands are prohibited when the configuration lock is applied:
•
Set kWh, kVARh, kVAh register
•
Clear all energy registers
•
Set status 1 or 2 count
•
Clear energy log
•
Force KYZ output on, off, or clear force
•
Restore factory defaults
•
Reset power monitor system
Setup
No setup is needed.