Operation
The KYZ output can operate in any of the following modes:
•
Energy pulse operation with fixed pulse width or toggle
•
Forced operation
Setup
KYZ-output set-up parameters are found in the Advanced Setup menu and are summarized in
the table.
Commands
•
Force KYZ Output On
•
Force KYZ Output Off
•
Remove Force from KYZ
Related Functions
•
Configuration lock
Parameter
Description
Range
Default
User
Setting
Model
TR
1
TR
2
E
M
1
E
M
2
E
M
3
KYZ Output
Parameter
0 = Disable
1 = Wh Fwd
2 = Wh Rev
0…2
0
• • •
3 = VARh Fwd
4 = VARh Rev
5 = VAh
0…5
• •
KYZ Output Scale The increase in value of the
selected parameter that caused
the output to change state
1…
100,000
1000
• • •
KYZ Pulse
Duration Setting
0 = toggle output
50…1000 = duration of output
pulse, rounded to 10 ms
0 or 50…
1000
250 ms
• • •