Electrical ratings – Rockwell Automation 1503VC IntelliVAC Contactor Control Module User Manual
Page 9
![background image](/manuals/578468/9/background.png)
Product Description
1-5
1503-UM051D-EN-P – June 2013
Table 1.A – Electrical Ratings
Main Input Voltage
(L1 to L2/N)
AC – 110 to 240 V rms, +10/-15%, 47 to 63 Hz
DC – 110 to 250 V, +10/-15%
Description
Contactor Ratings
(Amps)
Control Voltage
(AC or DC)
AC Rating
DC Rating
Inrush Current
400/800
120/240
25 A peak
(1/2 cycle)
25 A peak
Idle Current
(Maximum without contactor
coil energized)
400/800
120/240
125 mA
35 mA
Hold Current (maximum)
400/800
120/240
300 mA
100 mA
120
4.6 A
3.6 A
400
240
3.4 A
3.3 A
120
11.3 A
4.8 A
Close Current
(0.2 sec)
800
240
8.9 A
4.5 A
120
7.0 A
3.7 A
400
240
3.6 A
2.0 A
120
7.0 A
3.3 A
Main Input Current
(L1 to L2/N)
Trip Current (latch)
(0.2 sec)
800
240
4.3 A
1.9 A
Command Inputs
\
AC – 100 to 240 V rms
DC – 24 to 250 V
Maximum on state current for open or close command:
9mA
AC
@ 250 V AC, 60Hz, T
A
=60°C
9mA
DC
@ 250 V DC, T
A
=60°C
Minimum on state current for open or close command:
2mA
AC
@ 100 V AC, 60Hz, T
A
=60°C
600µA
DC
@ 24 V DC, T
A
=60°C
Maximum off state current for open or close command:
400µA
AC
@ 11 V AC, 60Hz, T
A
=60°C
400µA
DC
@ 15 V DC, T
A
=60°C
Status Output
Contacts
AC – 250 V rms, 5 A, R load; 2 A (reactive), PF=0.4
DC – 30 V, 5 A, R load; 2 A (reactive), L/R=7 ms
Standards and
Approvals
CE
, cULus, CSA, IEC pending
T
A =
Ambient Temperature
Refer to Chapter 6 for suitable EMC filter needed to meet CE requirements.
Also refer to Chapter 3 for EMC filter installation guidelines.
Please consult Factory for DC input current ratings.
Includes idle current.
\
Ensure compatibility of IntelliVAC input ratings with those of circuit components activating these inputs.
Consider means of isolating/loading these signals, as required (using interposing relays or load resistors.)
Consult factory for assistance, if needed.