Installation and Wiring

1503-UM051D-EN-P – June 2013

Three-Wire

Control

If using three-wire control, the CLOSE contactor input is maintained

high using two contacts. Momentarily opening this input will cause

the IntelliVAC to open the contactor. Momentarily closing the

START contact will provide a CLOSE command to IntelliVAC

(given that all permissives are satisfied).

In this configuration, the STATUS output acts as a seal-in contact. If a

fault occurs, in addition to cycling control power over to the IntelliVAC

module, the CLOSE command must be removed for a minimum of 4

seconds before being re-applied. Refer to Figure 3.10.

Refer to Table 3.A for recommended fuse sizing.