Intellivac features, Description (cont.), Figure 1.2 – intellivac block diagram – Rockwell Automation 1503VC IntelliVAC Contactor Control Module User Manual
Page 6
![background image](/manuals/578468/6/background.png)
1-2
Product Description
1503-UM051D-EN-P – June 2013
Description (cont.)
Micro Controller
C
o
n
ta
c
to
r C
o
il(s
)
In
te
rfa
c
e
Configuration
Inputs
(DIP
switches)
Command
Inputs
Current
Regulator
IGBT Coil
Switching
CC
Input
Power
Conditioning
Coil
Cur
re
n
t T
ransducer
Vacuum Contactor
Close Coil
Vacuum Contactor
Trip Coil
Supply
Voltage
110-240
VAC
or
110-250
VDC
Close
Signal
Open
Signal
Vacuum Contactor
Auxiliary
C
C
External
Capacitor
(Optional)
Module
Status
Contactor
Status
Au
x.
Feedback
St
atus
Output
s
c
Altitude
Select
Drop-Out
Select
TDUV
Time
Select
Contactor
Select
c
c
c
c
c
c
c
c
c
c
c
Flash EEPROM
Interface
Coil
Power
Supply
Control
Power
Supply
Power Up
Safety
c
c
c
Figure 1.2 – IntelliVAC Block Diagram
IntelliVAC Features
A wide range of supply voltage (110 – 240 V AC 50/60 Hz,
110 - 250 V DC) allows implementation in multiple applications
Consistent vacuum contactor pick-up time (at a given supply
voltage) ensures repeatable performance
Selectable vacuum contactor drop-out time improves
coordination with upstream power fuses
Electronic altitude compensation (400 A only) eliminates
mechanical compensation required for altitudes above 1,000
meters (800 A contactors include a user-friendly altitude
adjustment)
Power loss ride-through (TDUV) allows the vacuum contactor
to remain closed during short power loss (may require an
optional external capacitor, dependant on ride-through time)