Specifications, Mounting and connections, Configuration – Rockwell Automation 1503VC IntelliVAC Contactor Control Module User Manual
Page 8: Firmware
![background image](/manuals/578468/8/background.png)
1-4
Product Description
1503-UM051D-EN-P – June 2013
Specifications
Mounting
&
Connections
The IntelliVAC
control modules are mounted using two (2) screws
(see Figure 1.3). They are typically located in the low voltage
control panel of the medium voltage controller (Bulletin 1500/1900
controllers, in the case of Rockwell Automation).
IntelliVAC is interfaced to the Bulletin 1502 vacuum contactors
using a “quick” connector, located at the module, a wire harness
and “quick” connector at the contactor. Control power and other
control circuit connections are similarly achieved with “quick”
connectors.
Configuration
IntelliVAC
is easily configured for a wide variety of medium
voltage motor and feeder control applications. It is configured
using DIP switches, located within the enclosure (front side).
Please refer to Chapter 4 for information.
Bulletin 1500/1900 controllers are shipped with IntelliVAC
pre-
configured for the required application. Please refer to the
documents provided with the order.
Firmware
IntelliVAC
has firmware stored in flash EEPROM; therefore, this
may be updated in the field (if necessary). The IntelliVAC
board
firmware is updated using the mini-DIN connector, which is
accessible inside the enclosure.