Rockwell Automation 1503VC IntelliVAC Contactor Control Module User Manual
Page 35
Monitoring and Troubleshooting
5-3
1503-UM051D-EN-P – June 2013
Table 5.B – IntelliVAC Status Indication (Series B design)
Module Status
Contactor Status
Conditions
XY
Description
LED Color
Relay
LED Color
Relay
Normal
Healthy Module and Contactor OPEN
Green
Closed
Off
Open
Normal
Healthy Module and Contactor CLOSED
Green
Closed
Yellow
Closed
Warning
Invalid Command Present ^
Yellow
Closed
Off
Open
Warning
Mechanical Latch Fail to Trip
Yellow
Open
Yellow
Closed
Fault
Power Up with Contactor CLOSED
Red – Flash 2 [
Open
Yellow
Closed
Fault
Contactor Fails to Pick Up
Green
Open
Red – Flash 1 Z
Open
Fault
Contactor Drop Out During Hold
Green
Open
Red – Flash 2 [
Open
Fault
Long Contactor Drop Out Time
Green
Open
Red – Flash 3 Z
Open
Fault
Microcontroller Malfunction
Red
Open
Red
Open
Fault
Power Up with Invalid Dip Switch Configuration
Red – Flash 1
Open
Off
Open
Fault
Undervoltage with a CLOSE Command Present
Red
Open
Off
Open
X
Warning = Recoverable Condition – Remove and retry offending signal
Y
Fault = Non-recoverable condition – Module power must be removed and re-applied.
Z
Flash 1 = 1 Flash Red LED followed by a pause.
[
Flash 2 = 2 Consecutive Red LED flashes followed by a pause.
\
Flash 3 = 3 Consecutive Red LED flashes followed by a pause.
]
EH = Only for Electrically Held Contactor
^
Invalid Command Types:
1. Close, Jog or Trip commands present during power up sequence.
2. Close or Jog command re-applied too quickly (before contactor opening sequence is verified).
Allow at least 60 msec, plus drop out delay time, before re-applying these signals.
NOTE:
Contactor will only respond to a close command re-applications after the re-start delay timer has expired.
3. Close and Trip commands present simultaneously (valid with Mechanical Latch contactors only).