Installation and Wiring

3-9

1503-UM051D-EN-P – June 2013

Table 3.B – Terminal Assignments for IntelliVAC Interface Connections

X

Terminal No.

Terminal Designation

Description

1

External capacitor (negative) Y

2

External capacitor (positive) Y

Power connection for TDUV or capacitor

trip options only

3

Latch trip coil (common) Y

4

Latch trip coil Y

Output for mechanical latch contactor trip

coil

5

Close coil (common)

6

Close coil

Output to close coil of electrically held &

mechanical latch contactors

7

Open / Jog command Y Z

8

Open / Jog command (common) Y Z

Input to open a mechanical latch contactor

or jog an electrically held contactor

(mutually exclusive)

9

Close command Z

10

Close command (common) Z

Input to initiate the closure of electrically

held & mechanical latch contactors

11

Contactor auxiliary contact Z

12

Contactor auxiliary contact Z

Input to indicate the state of the contactor

(typically wired to a normally closed

auxiliary contact)

X

Refer to Table 1.A for electrical ratings.

Y

No connection required if option is not used.

Z

Ensure compatibility of IntelliVAC input ratings with those of circuit components activating these inputs.

Consider means of isolating/loading these signals, as required (using interposing relays or load resistors).

Consult factory for assistance, if needed.