Safety specifications – Rockwell Automation 1412-PP21xx PowerPad Portable Powermonitor User Manual
Page 78
78
Rockwell Automation Publication 1412-UM001D-EN-P - September 2012
Appendix B
Specifications
Safety Specifications
1200 Amp AC Current Probe
(Base Unit Accuracy Included)
Attribute
1412-PP2127
Electrical Safety (per EN 61010-1)
Double insulation
600V rms, Category IV, Pollution Degree 2
Electromagnetic Compatibility
Immunity and Emission
EN 61236-1 amendment 1
Electrostatic Discharges
IEC 1000-4-2
Radiation Field Resistance
IEC 1000-4-3
Fast Transients Resistance
IEC 1000-4-4
Electric Shock Resistance
IEC 1000-4-5
Conducted RF Interference
IEC 1000-4-6
Mechanical Protection
Shock and Vibration
EN 61010-1
IP 50
EN 60529 (electrical IP2X for the terminals)
Attribute
1412-PP2137-02
Nominal Range
1000 A AC for f 1 kHz
Measurement Range
3 A … 1200 A AC max (I > 1000 A not continuously)
(1)
(1) Currents < 0.5 A are displayed as zero on the PowerPad unit with this probe.
Probe Output Signal
1 mV AC/A AC
Maximum Clamping Diameter
52 mm (2 in.)
Safety
EN 61010-2-032, 600V, Category IV, Pollution Degree 2
Attribute
1412-PP2137-02
Ambient temperature
23 °C (73 °F) ± 3 °C (5 °F)
Humidity
20 … 75% of RH
Frequency
48 … 65 Hz
Distortion factor
< 1% no DC current
Magnetic field of external origin
< 40 A/m (earth's magnetic field)
Primary current
(A ac)
3 … 10 A
10 … 100 A
100 … 1200 A
Accuracy (% of the output
signal)
0.8% ± 1 ct
0.3% ± 1 ct
0.2% ± 1 ct
Phase shift (°)
1 °
0.5°
0.3°