Rockwell Automation Publication 1502-UM052H-EN-P - June 2013

45

Maintenance

Chapter 4

Figure 36 - Auxiliary Contact Adjustment

2. Slide the clamping fixture (part number 80154-149-51) over the top of the

armature stop bracket (

Figure 37

). Finger-tighten the two outside fixture

mounting bolts against the armature stop bracket. You may have to push
the armature plate a little to the rear to put the clamp in place.

Figure 37 - Clamping Contactor Closed

3. Place a 5/8” wrench on the main shaft of the contactor, pull down and

close the contactor (

Figure 38

) while finger-tightening the top middle

screw on the clamping fixture. (Case should be taken not to bend the
actuator stop plate).

Auxiliary Assembly

Retaining Bolt

Contactor Clamping Fixture