Drive rear bus-bar kit installation – Rockwell Automation 20G PowerFlex 750-Series Power Option Cabinets User Manual

Page 26

background image

26

Rockwell Automation Publication 750-IN030B-EN-P - October 2014

PowerFlex 750-Series Power Option Cabinets

Drive Rear Bus-bar Kit
Installation

Drive rear bus-bar kits provide an AC and DC line input power and AC motor
connection point behind the drive’s extruded bus-bar.

Reuse the drive’s L-brackets.

Table 22 - 20-750-PBAY-RBRK-2 Kit Contents

1. Assemble the M10 carriage bolts and clamp plates.
2. Slide the bolt assemblies into the cannel of the drive’s extruded bus-bar.

3. Align the four bolts on the drive rear bus-bar.
4. Tighten M10 nuts to 38.0 N•m (336 lb•in).

Description

Part No.

Quantity

Drive Rear Bus-bar

1

M10 x 45 mm Carriage Bolt

29220-903-02

4

Bus-bar Clamp Plate

PN-37764

4

M10 Nut with Washer

29355-002-01

4

IMPORTANT

Verify that clamp fits squarely in the bus-bar slot.