beautypg.com

Remove power from all equipment, Powerflex 755 drive – Rockwell Automation 20G PowerFlex 750-Series Power Option Cabinets User Manual

Page 10

background image

10

Rockwell Automation Publication 750-IN030B-EN-P - October 2014

PowerFlex 750-Series Power Option Cabinets

Remove Power from All
Equipment

Remove power from all energized equipment before proceeding with these
instructions. Refer to the product’s installation instructions and review all safety
precautions before performing work on this equipment.

PowerFlex 755 Drive

1. Turn off and lock out all input power, including any and all external power

sources.

2. Wait 15 minutes and verify that there is no voltage at the drive’s input

power terminals.

3. Measure the DC bus voltage at the -DC and +DC TESTPOINT sockets

on the front of the power module.

Figure 1 - PowerFlex Drive -DC and +DC Testpoint Sockets

ATTENTION: To avoid an electric shock hazard, verify that the voltage on the
bus capacitors has discharged completely before servicing. Measure the DC bus
voltage at the -DC and +DC TESTPOINT sockets on the front of the power
module (see

Figure 1

for location).

Frame 8 AC Input Drive Shown

This manual is related to the following products: