Chapter 4 Troubleshooting
Table 16 - LED Fault Indication & Diagnostics
Flashes Fault Type
Possible Fault Explanations
Possible Solutions
1
Overload
• Motor overload condition present.
• FLA dial adjustment is not matched to motor type.
• Check for motor overload condition.
• Verify actual motor current does not exceed FLA.
• Verify/reset the FLA dial adjustment.
• Program/modify the Overload setting for load or duty
cycle required.
2
Over-Temperature • Controller ventilation blocked.
• Controller duty cycle exceeded.
• Cooling fan not working.
• Ambient temperature exceeded.
• Failed control module.
• Over-current condition with Overload disabled.
• Check for proper ventilation.
• Verify duty cycle.
• Connect or replace cooling fan.
• Wait for controller to cool or provide external coolin.
• Replace control module.
3
Phase Reversal
• Incoming supply voltage is not the expected sequence.
• Check power wiring.
• Adjust dip switch #9 for desired sequence.
4
Phase Loss/
Open Load
• Missing Supply Phase.
• Missing or unable to detect motor connection.
• Check for open line (i.e. open fuse).
• Check for incorrect wiring to load.
• Verify proper operation of the fault contactor.
• Verify connection type to motor (LINE or DELTA).
• Ensure product is sized correctly for motor.
5
Phase Imbalance
• Unbalanced Phase Currents (> 65% differential).
• Incoming line voltage problem.
• Check motor current in each phase to verify imbalance.
Motor current imbalance can indicate potential motor
problem.
6
Shorted SCR
• Shorted SCR.
• Welded or latched bypass contactor.
• Verify connection type (LINE or DELTA) and verify setting.
• Perform continuity check across power poles (L1 – T1, L2
– T2, L3 – T3). Measurements should exceed 10 k ohms.
For best results, remove line and load motor connections.
• Cycle power to device and attempt to restart. If fault
persists, replace device.
7
Test
• Intended operation.
• Reset fault.
12
Check Sum
• Internal software corruption.
• Replace device.