Motor fla requirements, Figure 9 - fla setting of motor, Motor overload trip curves – Rockwell Automation 150-E SMC Elevator Users Manual User Manual
Page 21: Figure 10 - trip class

Rockwell Automation Publication 150-UM009D-EN-P- February 2011
21
Programming Chapter 3
Motor FLA Requirements
The front of the SMC controller contains a dial which is used for setting the
actual FLA of the motor. The label is designed to accommodate motors
connected in the LINE or DELTA mode. To determine the proper setting, look
at the motor’s nameplate and set the dial accordingly. The dial setting can be
modified depending on the service factor of the motor.
Figure 9 - FLA Setting of Motor
Motor Overload Trip Curves
The trip class should be set according to the motor’s maximum permissible locked
rotor time or the general thermal capabilities. Consult the motor manufacturer
for recommendations on setting the trip class.
Figure 10 - Trip Class
∆ 32
19
Delta FLA
Line FLA
∆ 11
7
∆ 22
13
Service Factor _ _
FLA _ _
Service Factor < 1.15
Service Factor ≥ 1.15
= 0.9 X FLA
= 1.0 X FLA
= 1.0 X FLA
OR
Maximum Continuous Rated
(MCR) Motors
Class 10
Class 15
Class 20
Multiple of FLA
t (sec)
8
10
6
4
2
1
1000
100
10
1
0.1
800
600
400
200
80
60
40
20
8
6
4
2
0.2
0.4
0.6
0.8
8
10
6
4
2
1
8
10
6
4
2
1
1000
100
10
1
0.1
800
600
400
200
80
60
40
20
8
6
4
2
0.2
0.4
0.6
0.8
1000
100
10
1
0.1
800
600
400
200
80
60
40
20
8
6
4
2
0.2
0.4
0.6
0.8
COLD START
HOT START