Chapter 3 Programming
Table 9 - Phase Rotation
Table 10 - Phase Imbalance
Table 11 - Overload Trip Class
Table 12 - Overload Reset
Table 13 - Aux #1 Setting
Table 14 - Motor Connection Type
Table 15 - Stop Delay
Setting
Switch #9
The allowable phase rotation of the motor is defined by this switch.
ABC rotation
OFF
CBA rotation
ON
Setting
Switch #10
The controller has the ability to monitor for imbalance between phase
currents. This protection feature can be user-disabled.
Enabled
OFF
Disabled
ON
Setting Switch #11 Switch #12
The controller incorporates, as standard, electronic
overload protection. This motor overload protection is
accomplished electronically with the use of internal current
transformers on each of the three phases. The controller’s
overload protection is programmable, providing the user
with flexibility.
OFF
OFF
OFF
10
ON
OFF
15
OFF
ON
20
ON
ON
Setting Switch #13 In manual reset mode, the fault can only be reset by pushing the ‘Push to
Reset’ button on the front of the controller. In auto reset mode, the unit will
automatically reset when the unit determines the motor has cooled to 75%
of its thermal capacity.
Manual
OFF
Auto
ON
Setting
Switch #14 The operation defines the operation of the Auxiliary contacts. Normal
mode means that the contact will change state immediately when a
start/run command is given. Up-to-Speed mode means that the contact
will change state only when the controller is in bypass. Aux#2, when
added, will operate opposite of this programming.
Normal
OFF
Up-to-Speed ON
Setting Switch #15
In DELTA connection mode, the device is designed to control a 6 or 12 lead
motor. In LINE connection mode, the device is designed to control a 3 or 9
lead motor.
Delta
OFF
Line
ON
Setting(seconds)
Switch #16
When the delay is programmed, the motor will continue to run
for the programmed period of time after the run command is
removed from the controller.
0.0
OFF
0.75
ON