Rockwell Automation Publication 150-UM009D-EN-P- February 2011

Chapter 3 Programming

Table 9 - Phase Rotation

Table 10 - Phase Imbalance

Table 11 - Overload Trip Class

Table 12 - Overload Reset

Table 13 - Aux #1 Setting

Table 14 - Motor Connection Type

Table 15 - Stop Delay

Setting

Switch #9

The allowable phase rotation of the motor is defined by this switch.

ABC rotation

OFF

CBA rotation

ON

Setting

Switch #10

The controller has the ability to monitor for imbalance between phase
currents. This protection feature can be user-disabled.

Enabled

OFF

Disabled

ON

Setting Switch #11 Switch #12

The controller incorporates, as standard, electronic
overload protection. This motor overload protection is
accomplished electronically with the use of internal current
transformers on each of the three phases. The controller’s
overload protection is programmable, providing the user
with flexibility.

OFF

OFF

OFF

10

ON

OFF

15

OFF

ON

20

ON

ON

Setting Switch #13 In manual reset mode, the fault can only be reset by pushing the ‘Push to

Reset’ button on the front of the controller. In auto reset mode, the unit will
automatically reset when the unit determines the motor has cooled to 75%
of its thermal capacity.

Manual

OFF

Auto

ON

Setting

Switch #14 The operation defines the operation of the Auxiliary contacts. Normal

mode means that the contact will change state immediately when a
start/run command is given. Up-to-Speed mode means that the contact
will change state only when the controller is in bypass. Aux#2, when
added, will operate opposite of this programming.

Normal

OFF

Up-to-Speed ON

Setting Switch #15

In DELTA connection mode, the device is designed to control a 6 or 12 lead
motor. In LINE connection mode, the device is designed to control a 3 or 9
lead motor.

Delta

OFF

Line

ON

Setting(seconds)

Switch #16

When the delay is programmed, the motor will continue to run
for the programmed period of time after the run command is
removed from the controller.

0.0

OFF

0.75

ON