Quick start – Rockwell Automation 20-750-PBUS Profibus DPV1 Option Module User Manual
Page 17
Rockwell Automation Publication 750COM-UM004B-EN-P - September 2012
17
Getting Started Chapter 1
Quick Start
This section is provided to help experienced users quickly start using the Option
Module. If you are unsure how to complete a step, refer to the referenced chapter.
Step Action
See
1
Review the safety precautions for the option module.
Throughout this manual
2
Verify that the PowerFlex drive is properly installed.
PowerFlex 750-Series AC Drive
Installation Instructions,
publication
3
Install the option module.
a. Verify that the PowerFlex drive is not powered.
b. Insert the option module in drive Port 4, 5 or 6. Use
the captive screws to secure and ground the option
module to the drive.
c. Connect the option module to the network by using
a Profibus cable.
Important: When another module (I/O, encoder,
communication, and so forth) resides in the adjacent port
to the left of the 20-750-PBUS option module—and the
lower mounting screw of that module is a larger T15 Torx
head screw, perform additional steps 2a through 2d on
Network Communication Option
Card Installation Instructions,
publication
and
4
Apply power to the option module.
a. The option module receives power from the drive.
Verify that the option module is installed correctly
and then apply power to the drive. The status
indicators should be green. If they flash red, there is
a problem. See
b. Configure and verify key drive parameters.
5
Configure the option module for your application.
Set option module parameters for the following functions
as required by your application:
• Node address
• I/O configuration
• Master-Slave hierarchy
• Fault actions
6
Configure the Profibus Master to communicate with the
option module.
Use controller configuration tools such as Prosoft
Configuration Builder software for Profibus and RSLogix
5000 software to configure the master on the Profibus
network to recognize the option module and drive.
Configuring the Profibus Master
7
Configure the I/O.
Use a controller configuration tool such as RSLogix 5000
software that enables you to control the option module
and connected drive using I/O.