Chapter 7
RSLogix 5000 Controller Tags
• CRN
– The Configuration Revision Number is used internally with
RSLogix for configuration information. The user does not need to use this
tag.
• Pt00FaultMode
– The Pt00FaultMode is used in conjunction with
FaultValue to configure the state of output 0 when a communications fault
occurs. A value of 0 means that, in the case of a communications fault, the
value in FaultValue will be used (Off or On). A value of 1 means that the
last state will be held. By default this value is 0.
• Pt00FaultValue
– The Pt00FaultValue is used in conjunction with
FaultMode to configure the state of output 0 when a communications fault
occurs. A value of 0 is Off, and a value of 1 is On. By default the value is 0.
• Pt00FilterOffOn
– The Pt00FilterOffOn is used to determine the Off to
On delay time for input point 0 before the interface considers the input
point on or True. A value of 0 indicates there is no delay from an off
condition to an on condition; the only delay would be a hardware delay. A
value >0 would delay the input turning on by the configured value in
milliseconds. By default this value is 0.
• Pt00FilterOnOff
– The Pt00FilterOnOff is used to determine the On to
Off delay time for input point 0 before the interface considers the input
point off or False. A value of 0 indicates there is no delay from an on to off
condition; the only delay would be a hardware delay. A value >0 would
delay the input turning off by the configured value in milliseconds. By
default this value is 0.
• Pt00NoLoadEn
– The Pt00NoLoadEn is used to enable or disable No
Load diagnostic detection for output 0. A value of 1 means that No Load
diagnostic detection is enabled. A value of 0 means that No Load
diagnostic detection is disabled. By default this value is 0.
• Pt00OpenWireEn
– The Pt00OpenWireEn is used to enable or disable
the open wire detection for input point 0. A value of 1 means that open
wire detection is enabled. A value of 0 means that open wire detection is
disabled. By default this value is 1.
• Pt00OutputShortCircuitEn
– The Pt00OutputShortCircuitEn is used
to enable or disable the short circuit detection for output point 0. A value
of 1 means that short circuit detection is enabled. A value of 0 means that
short circuit detection is disabled. By default this value is 0.
• Pt00ProgMode
– The Pt00ProgMode is used in conjunction with
ProgValue to configure the state of output 0 when the controller is in
Program mode. A value of 0 means that the ProgValue (Off or On) will be
used when the controller is in Program mode. A value of 1 means that the
last state will be held. By default this value is 0.
• Pt00ProgValue
– The Pt00ProgValue is used in conjunction with
ProgMode to configure the state of output 0 when the controller is in
Program mode. A value of 0 is Off, and a value of 1 is On. By default this
value is 0.
• Pt00ShortCircuitEn
– The Pt00ShortCircuitEn is used to enable or
disable the short circuit detection for input point 0. A value of 1 means
that short circuit detection is enabled. A value of 0 means that short circuit
detection is disabled. By default this value is 0.