Powerflex 700s drives, Logic command word (phase ii control) – Rockwell Automation 20-COMM-L LonWorks Adapter User Manual
Page 69
Logic Command/Status Words
C-3
20-COMM-L LonWorks Adapter User Manual
Publication 20COMM-UM008B-EN-P
PowerFlex 700S Drives
Logic Command Word (Phase II Control)
Logic Bits
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0 Command
Description
x Normal Stop
0 = Not Normal Stop
1 = Normal Stop
x
Start
(1)
0 = Not Start
1 = Start
x
Jog 1
0 = Not Jog using [Jog Speed 1] (Par. 29)
1 = Jog using [Jog Speed 1] (Par. 29)
x
Clear Fault
(2)
0 = Not Clear Fault
1 = Clear Fault
x
x
Unipolar Direction 00 = No Command
01 = Forward Command
10 = Reverse Command
11 = Hold Direction Control
x
Reserved
x
Jog 2
0 = Not Jog using [Jog Speed 2] (Par. 39)
1 = Jog using [Jog Speed 2] (Par. 39)
x
Current Limit Stop 0 = Not Current Limit Stop
1 = Current Limit Stop
x
Coast Stop
0 = Not Coast to Stop
1 = Coast to Stop
x
Reserved
x
Reserved
x
Spd Ref Sel0
x
Spd Ref Sel1
x
Spd Ref Sel2
x
Reserved
(1)
A Not Stop condition (logic bit 0 = 0, logic bit 8 = 0, and logic bit 9 = 0) must first be present before a 1 = Start condition starts the drive.
(2)
To perform this command, the value must switch from ‘0’ to ‘1’.
Bits
14 13 12
0
0
0 = Spd Ref A (Par. 27)
0
0
1 = Spd Ref B (Par. 28)
0
1
0 = Preset 2 (Par. 15)
0
1
1 = Preset 3 (Par. 16)
1
0
0 = Preset 4 (Par. 17)
1
0
1 = Preset 5 (Par. 18)
1
1
0 = Preset 6 (Par. 19)
1
1
1 = Preset 7 (Par. 20)