Powerflex 700s drives, Logic command word (phase ii control) – Rockwell Automation 20-COMM-L LonWorks Adapter User Manual

Page 69

background image

Logic Command/Status Words

C-3

20-COMM-L LonWorks Adapter User Manual

Publication 20COMM-UM008B-EN-P

PowerFlex 700S Drives

Logic Command Word (Phase II Control)

Logic Bits

15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0 Command

Description

x Normal Stop

0 = Not Normal Stop

1 = Normal Stop

x

Start

(1)

0 = Not Start

1 = Start

x

Jog 1

0 = Not Jog using [Jog Speed 1] (Par. 29)

1 = Jog using [Jog Speed 1] (Par. 29)

x

Clear Fault

(2)

0 = Not Clear Fault

1 = Clear Fault

x

x

Unipolar Direction 00 = No Command

01 = Forward Command

10 = Reverse Command

11 = Hold Direction Control

x

Reserved

x

Jog 2

0 = Not Jog using [Jog Speed 2] (Par. 39)

1 = Jog using [Jog Speed 2] (Par. 39)

x

Current Limit Stop 0 = Not Current Limit Stop

1 = Current Limit Stop

x

Coast Stop

0 = Not Coast to Stop

1 = Coast to Stop

x

Reserved

x

Reserved

x

Spd Ref Sel0

x

Spd Ref Sel1

x

Spd Ref Sel2

x

Reserved

(1)

A Not Stop condition (logic bit 0 = 0, logic bit 8 = 0, and logic bit 9 = 0) must first be present before a 1 = Start condition starts the drive.

(2)

To perform this command, the value must switch from ‘0’ to ‘1’.

Bits

14 13 12

0

0

0 = Spd Ref A (Par. 27)

0

0

1 = Spd Ref B (Par. 28)

0

1

0 = Preset 2 (Par. 15)

0

1

1 = Preset 3 (Par. 16)

1

0

0 = Preset 4 (Par. 17)

1

0

1 = Preset 5 (Par. 18)

1

1

0 = Preset 6 (Par. 19)

1

1

1 = Preset 7 (Par. 20)