20-COMM-L LonWorks Adapter User Manual
Publication 20COMM-UM008B-EN-P
Appendix
B
Adapter Parameters
Appendix B provides information about the adapter parameters.
About Parameter Numbers
The parameters in the adapter are numbered consecutively.
Parameter List
Topic
Page
Configuration Tool
Numbering Scheme
• HIM
• DriveExplorer
• DriveExecutive
The adapter parameters begin with parameter 01. For example,
Parameter 01 - [DPI Port] is parameter 01 as indicated by this manual.
Parameter
No. Name and Description
Details
01
[DPI Port]
Displays the port to which the adapter is connected.
This usually is port 5.
Minimum:
0
Maximum:
7
Type:
Read Only
02
[DPI Data Rate]
Displays the data rate used by the drive. This data rate
is set in the drive and the adapter detects it.
Values:
0 = 125 kbps
1 = 500 kbps
Type:
Read Only
03
[Ref/Fdbk Size]
Displays the size of the Reference/Feedback. The
drive determines the size of the Reference/Feedback.
Values:
0 = 16-bit
1 = 32-bit
Type:
Read Only
04
[Datalink Size]
Displays the size of each Datalink word. The drive
determines the size of Datalinks.
Values:
0 = 16-bit
1 = 32-bit
Type:
Read Only
05
[Reset Module]
No action if set to ‘0’ (Ready). Resets the adapter if set
to ‘1’ (Reset Module). Restores the adapter to its
factory default settings if set to ‘2’ (Set Defaults). This
parameter is a command. It resets to ‘0’ (Ready) after
the command has been performed.
Default:
0 = Ready
Values:
0 = Ready
1 = Reset Module
2 = Set Defaults
Type:
Read/Write
Reset Required: No
!
ATTENTION: Risk of injury or equipment damage exists. If the adapter is
transmitting I/O that controls the drive, the drive can fault when you reset the
adapter. Determine how your drive will respond before resetting a connected
adapter.