Rockwell Automation 20-COMM-L LonWorks Adapter User Manual
Page 63

Adapter Parameters
B-3
20-COMM-L LonWorks Adapter User Manual
Publication 20COMM-UM008B-EN-P
09
[DPI I/O Cfg]
Sets the I/O that is transferred through the adapter.
NOTE: The Cmd/Ref bit must be set to control the
drive via the network. The respective Datalink bit(s)
must be set if the nvi/nvo Datalink variables are used.
Default:
xxx0 0001
Bit Values:
0 = I/O disabled
1 = I/O enabled
Type:
Read/Write
Reset Required: Yes
10
[DPI I/O Act]
Displays the I/O that the adapter is actively
transmitting. The value of this parameter is usually
equal to the value of
Parameter 9 - [DPI I/O Cfg].
Default:
xxx0 0001
Bit Values:
0 = I/O disabled
1 = I/O enabled
Type:
Read Only
11
[Flt Cfg Logic]
Sets the Logic Command data that is sent to the drive
if
Parameter 6 - [Comm Flt Action] is set to ‘4’ (Send
Flt Cfg) and communication is disrupted.
The bit definitions depend on the product to which the
adapter is connected. See
documentation for the drive being used.
Default:
0000 0000 0000 0000
Minimum:
0000 0000 0000 0000
Maximum:
1111 1111 1111 1111
Type:
Read/Write
Reset Required: No
12
[Flt Cfg Ref]
Sets the Reference data that is sent to the drive if
Parameter 6 - [Comm Flt Action] is set to ‘4’ (Send
Flt Cfg) and communication is disrupted.
NOTE: This is a linear engineering unit value where ‘0’
equals 0 Hz. and 32,767 equals the Hz. value in the
PowerFlex 7-Class drive parameter 55 - [Maximum
Freq].
Default:
0
Minimum:
0
Maximum:
4294967295
Type:
Read/Write
Reset Required: No
Important: If the drive uses a 16-bit
Reference, the most significant word of
this value must be set to zero (0) or a
fault will occur.
13
14
15
16
17
18
19
20
[Flt Cfg A1 In]
[Flt Cfg A2 In]
[Flt Cfg B1 In]
[Flt Cfg B2 In]
[Flt Cfg C1 In]
[Flt Cfg C2 In]
[Flt Cfg D1 In]
[Flt Cfg D2 In]
Sets the data that is sent to the Datalink in the drive if
Parameter 6 - [Comm Flt Action] is set to ‘4’ (Send
Flt Cfg) and communication is disrupted.
NOTE: These are 32-bit values. If 16-bit Datalinks are
active, only the least significant word is used. If the
32-bit value is out of range for a 16-bit Datalink, a
configuration error forces a correction before I/O can
be enabled.
Default:
0
Default:
0
Default:
0
Default:
0
Default:
0
Default:
0
Default:
0
Default:
0
Minimum:
0
Maximum:
4294967295
Type:
Read/Write
Reset Required: No
Important: If the drive uses 16-bit
Datalinks, the most significant word of
this value must be set to zero (0) or a
fault will occur.
Parameter
No. Name and Description
Details
Bit
Definition
No
t Us
ed
No
t Us
ed
No
t Us
ed
Da
ta
link
D
Da
ta
link
C
Da
ta
link
B
Da
ta
link
A
Cmd/Ref
Default
x
x
x
0
0
0
0
1
Bit
7
6
5
4
3
2
1
0
Bit
Definition
No
t Us
ed
No
t Us
ed
No
t Us
ed
Da
ta
link
D
Da
ta
link
C
Da
ta
link
B
Da
ta
link
A
Cmd/Ref
Default
x
x
x
0
0
0
0
1
Bit
7
6
5
4
3
2
1
0