Bac-8007 draft7_ 7 – Titus Alpha BAC-8007/BAC-8207 Dual Duct User Manual
Page 5
BAC-8007 and BAC-8207 VAV Controllers
About the controllers
Specifications
5
Air flow sensor features
Configured as BACnet analog input object.
CMOS differential pressure 0-2 inches of water
(0-500 Pa) measurement range. Internally
linearized and temperature compensated.
Span accuracy 4.5% of reading.
Barbed connections for 1/4 FR tubing.
Range dependent upon DP pickup, tubing size/
length and connections.
Actuator specifications
Torque
40 in-lb. (4.5 N
•
m)
Angular rotation
0 to 95°
Adjustable end stops at 45° and 60° rotation
Motor timing,
BAC-8007 90 sec./90° at 60 Hz
108 sec./90° at 50 Hz
Motor timing,
BAC-8207 60sec./90° at 60 Hz
72 sec./90° at 50 Hz
Shaft size
Directly mounts on 3/8 to 5/8 inch (9.5 to 16 mm)
round or 3/8 to 7/16 inch (9.5 to 11 mm) square
damper shafts.
Regulatory
UL 916 Energy Management Equipment
FCC Class B, Part 15, Subpart B
BACnet Testing Laboratory listed as an application
specific controller (ASC).
UL 864 smoke controls (BAC-8207 only)
Installation
Supply voltage
24 volts AC, -15%, +20% 5 VA
Weight
13.2 ounces (376 grams)
Case material
Flame retardant plastic
Environmental limits
Operating
32 to 120°
F (0 to 49°
C)
Shipping
–40 to 140°
F (–40 to 60°
C)
Humidity
5–95% relative humidity (non-condensing)
Models
BAC-8007
Dual-duct VAV controller with 90 second actuator
BAC-8207
Dual-duct VAV controller with 60 second actuator
and UL 864 smoke control application