Installing the controller

Connecting an airflow sensor

19

Connecting an

airflow sensor

An airflow sensor is incorporated as one of the inputs to the controller. Remove
the plugs and connect the tubing from the pitot assembly to the airflow sensor
inputs next to the drive hub. (See Illustration 2-14). The airflow sensor is
programmed as Input 1.

Connecting

power

The controllers require an external, 24 volt, AC power source. Use the following
guidelines when choosing and wiring transformers.

Do not run 24 volt, AC power from within an enclosure to external

controllers.

Illustration 2-14 Airflow sensor inputs

Total airflow (high) Static airflow (low)

Illustration 2-15 Power terminals and jumper

Power

terminals

Use a Class-2 transformer of the appropriate size to supply power to

the controllers. Titus recommends powering only one controller from each

transformer.