Installing the controller
Connecting outputs
13
Connecting
outputs
The BAC-8007 and BAC-8207 controllers have eight preconfigured outputs to
support the supplied programs. Only six have externally available physical
terminals. All of the outputs are preconfigured for the application programs
supplied in the in the dual-duct controllers and are listed in Table 2-2.
Damper Clockwise and Clockwise The damper outputs are binary output
objects that control the motion of the internal damper.
Analog Heat The analog heat output controls modulating analog reheat. This
output is active only if the controller is set up for reheat. For staged reheat
applications, use an REE-5001 relay.
Table 2-2 BAC-8007 and BAC-8207output objects
Object Function
Name
False
value
True value
Default
value
Type
BO1
Damper Clockwise
DAMPER CW
Neutral
Clockwise
Neutral
Internal
BO2
Damper Counter
Clockwise
DAMPER CCW
Neutral
Counterclockwise Neutral
Internal
AO3
Analog Heat
ANALOG HEAT
0
0-10 VDC
AO4
Fan Speed
FAN SPEED
0
0-10 VDC
BO5
Fan Start/Stop
FAN
On
Off
Off
Triac
BO6
Secondary Damper
Clockwise
SEC DAMPER CW
Neutral
Clockwise
Neutral
Triac
BO7
Secondary Damper
Counterclockwise
SEC DAMPER CCW Neutral
Counterclockwise Neutral
Triac
BO8
Lighting
HEAT/LITE
On
Off
Off
Triac
Illustration 2-5 Modulating heat output