Installing the controller

Connecting outputs

13

Connecting

outputs

The BAC-8007 and BAC-8207 controllers have eight preconfigured outputs to
support the supplied programs. Only six have externally available physical
terminals. All of the outputs are preconfigured for the application programs
supplied in the in the dual-duct controllers and are listed in Table 2-2.

Damper Clockwise and Clockwise The damper outputs are binary output
objects that control the motion of the internal damper.

Analog Heat The analog heat output controls modulating analog reheat. This
output is active only if the controller is set up for reheat. For staged reheat
applications, use an REE-5001 relay.

Table 2-2 BAC-8007 and BAC-8207output objects

Object Function

Name

False

value

True value

Default

value

Type

BO1

Damper Clockwise

DAMPER CW

Neutral

Clockwise

Neutral

Internal

BO2

Damper Counter

Clockwise

DAMPER CCW

Neutral

Counterclockwise Neutral

Internal

AO3

Analog Heat

ANALOG HEAT

0

0-10 VDC

AO4

Fan Speed

FAN SPEED

0

0-10 VDC

BO5

Fan Start/Stop

FAN

On

Off

Off

Triac

BO6

Secondary Damper

Clockwise

SEC DAMPER CW

Neutral

Clockwise

Neutral

Triac

BO7

Secondary Damper

Counterclockwise

SEC DAMPER CCW Neutral

Counterclockwise Neutral

Triac

BO8

Lighting

HEAT/LITE

On

Off

Off

Triac

Illustration 2-5 Modulating heat output