BAC-8007 and BAC-8207 VAV Controllers

Installing the controller

Connecting outputs

14

Fan Speed Controls the speed of a variable speed fan if the controller is set up
for fan operation.

Fan Start/Stop The fan start output is preconfigured to either start or stop a
single speed fan or enable a multispeed fan. The output is a triac that can switch
up to 1 ampere at 24 volts AC.

Secondary Damper Clockwise and Counterclockwise The secondary damper
output terminals are preconfigured to control the position of the damper of a
TSP-8000 series actuator for dual-duct operation. The outputs are triacs that can
switch up to 1 ampere at 24 volts AC. See the section

Dual-duct connections on

page 24

.

Local lighting The lighting output is preconfigured to work with the motion
sensor in an STE-8201 sensor to automatically control lights located in the same
space as the VAV. The output is a triac that can switch up to 1 ampere at 24 volts
AC.

Illustration 2-6 Fan speed output

Illustration 2-7 Fan start output

Illustration 2-8 Lighting output