Installing the controller

Connecting to an MS/TP network

17

Note

The MS/TP terminals are labeled -A, +B and S. The S terminal is provided as a

connecting point for the shield. The terminal is not connected to the ground of

the controller. When connecting to controllers from other manufacturers, verify

the shield connection is not connected to ground.

Illustration 2-11 MS/TP network wiring

Redundant network

wiring for increased

reliability

Ground shield only at

one end of the segment.