About the controllers
Specifications
4
Outputs, analog
2
Key features
Output short protection
Configured as BACnet analog objects.
Standard units of measure
Connector
Spade connectors, 0.25 inch
Conversion
12–bit analog–to–digital conversion
Output voltage
0–10 volts DC
Output current
30 mA per output, 30 mA total for all analog
outputs
Outputs, binary
4 triacs for external equipment
2 for the internal actuator
Key features
Optically isolated triac output
Conversion
12–bit analog–to–digital conversion
Connector
Spade connectors, 0.25 inch
Output range
Maximum switching 24 VAC at 3 amperes
Communications
BACnet MS/TP
EIA–485 operating at rates up to 76.8 kilobaud.
Removable screw terminal block.
Wire size 12–24 AWG
Sensor jack
RJ-45 jack compatible with model STE-8000 and
STE-6000 models with RJ-45 jacks
Supported objects
See PIC statement for supported BACnet objects
Control Basic
5 program areas in BAC-8007
6 program areas in BAC-8207
PID loop objects
8
Value objects
60 analog, 32 binary, and 12 multistate
Memory
Programs and program parameters are stored in
nonvolatile memory.
Auto restart on power failure
Applications programs
Dual-duct VAV heating and cooling
Monitor CO2 to control indoor air quality
Control local lighting with motion sensing
Fan control
Balancing
UL 864 smoke controll (BAC-8207 only)
Titus Controls supply the BAC-8x07 with
programming sequences for dual-duct
VAV applications: