Bac-8007 draft7_14, Connecting inputs – Titus Alpha BAC-8007/BAC-8207 Dual Duct User Manual
Page 11
Installing the controller
Connecting inputs
11
Connecting
inputs
The BAC-8007 and BAC-8207 controllers have preconfigured analog inputs to
support the supplied programs. The inputs cannot be changed to binary or
accumulator inputs. Only six inputs have externally available physical
terminals. All of the inputs are preconfigured for the application programs
supplied in the dual-duct controllers and are listed in Table 2-1.
Discharge air temperature Connect a 10k , Type 3 thermistor temperature probe
to the discharge air temperature input. The input includes the internal pull-up
resistor. An STE-1405 sensor is suitable for this application. Follow the
instructions supplied with the sensor for installation. See
Temperature setpoints on
page 26
for setting up discharge air temperature limiting that requires this input
sensor.
Space Temperature Input The space temperature input is connected only
through the RJ-45 thermostat and sensor input jack. It is a configured as an
analog input for STE-6010, STE-6014, and STE-6017 sensors. If an STE-8000
sensor is connected to the controller, this input is ignored. See
Connecting to
sensors on page 18
.
Space Setpoint The space setpoint input is connected only through the RJ-45
thermostat and sensor input jack. It is a configured for the setpoint dials on
STE-6014 or STE-6017 sensors. If an STE-6010 or STE-8000 sensor is connected to
the controller, this input is ignored. See
Connecting to sensors on page 18
.
Table 2-1 BAC-8007 and BAC-8207 input objects
Object Function
Name
Unit Location
Pull up
AI1
Discharge Air Temperature DISCHARGE AIR
°F
Terminal block
10k
AI2
Space Temperature
SPACE SENSOR
°F
RJ-45
10k
AI3
Space Setpoint
SPACE SETPOINT
°F
RJ-45
10k
AI4
Primary Duct Pressure
PRIMARY DUCT
wc
Internal airflow sensor
N/A
AI5
Secondary Duct Pressure
SECONDARY DUCT wc
Terminal block
None
AI6
Secondary Damper Position SECONDARY POS
Volts Terminal block
10k
AI7
CO2
CO2
PPM
Terminal block
None
AI8
Primary Damper Position
PRIMARY POS
Volts Internal damper position N/A
Illustration 2-3 Discharge air temperature