Bac-8007 draft7_14, Connecting inputs – Titus Alpha BAC-8007/BAC-8207 Dual Duct User Manual

Page 11

background image

Installing the controller

Connecting inputs

11

Connecting

inputs

The BAC-8007 and BAC-8207 controllers have preconfigured analog inputs to
support the supplied programs. The inputs cannot be changed to binary or
accumulator inputs. Only six inputs have externally available physical
terminals. All of the inputs are preconfigured for the application programs
supplied in the dual-duct controllers and are listed in Table 2-1.

Discharge air temperature Connect a 10k , Type 3 thermistor temperature probe
to the discharge air temperature input. The input includes the internal pull-up
resistor. An STE-1405 sensor is suitable for this application. Follow the
instructions supplied with the sensor for installation. See

Temperature setpoints on

page 26

for setting up discharge air temperature limiting that requires this input

sensor.

Space Temperature Input The space temperature input is connected only
through the RJ-45 thermostat and sensor input jack. It is a configured as an
analog input for STE-6010, STE-6014, and STE-6017 sensors. If an STE-8000
sensor is connected to the controller, this input is ignored. See

Connecting to

sensors on page 18

.

Space Setpoint The space setpoint input is connected only through the RJ-45
thermostat and sensor input jack. It is a configured for the setpoint dials on
STE-6014 or STE-6017 sensors. If an STE-6010 or STE-8000 sensor is connected to
the controller, this input is ignored. See

Connecting to sensors on page 18

.

Table 2-1 BAC-8007 and BAC-8207 input objects

Object Function

Name

Unit Location

Pull up

AI1

Discharge Air Temperature DISCHARGE AIR

°F

Terminal block

10k

AI2

Space Temperature

SPACE SENSOR

°F

RJ-45

10k

AI3

Space Setpoint

SPACE SETPOINT

°F

RJ-45

10k

AI4

Primary Duct Pressure

PRIMARY DUCT

wc

Internal airflow sensor

N/A

AI5

Secondary Duct Pressure

SECONDARY DUCT wc

Terminal block

None

AI6

Secondary Damper Position SECONDARY POS

Volts Terminal block

10k

AI7

CO2

CO2

PPM

Terminal block

None

AI8

Primary Damper Position

PRIMARY POS

Volts Internal damper position N/A

Illustration 2-3 Discharge air temperature