III. Venting / Air Intake Piping

TABlE 1: AIR INTAkE / VENT SySTEM OPTIONS

WARNING

Do not use this boiler with galvanized, Type 04 or Type 1 stainless steel, non metallic or any other

non Al9-4C

®

based vent systems.

Do not use a barometric damper or drafthood with this appliance.
Do not use vent dampers with this boiler.
Moisture and ice may form on surfaces around termination. To prevent deterioration, surfaces should

be in good repair (sealed, painted, etc.).
This appliance needs fresh air for safe operation and must be installed so there are provisions for

adequate combustion and ventilation air.
Do not reduce size of air intake pipe.
Read, understand and follow combustion air instruction restrictions contained in the Pre-Installation

instructions of this manual.
Do not operate appliance where gasoline or other flammable vapors or liquids, or sources of hydro-

carbons (i.e. bleaches, cleaners, chemicals, sprays, paint removers, fabric softeners, etc.) are used,

stored and/or present in the air.
When installing vent pipe through chimney, no other appliance can be vented into the chimney.
Do not exceed maximum vent/air intake lengths. Refer to Table 4.

Option

Description

Additional

Vent Kit

Required

Part Number

Installation

Drawing and

Specification

(See Section)

1. Separate

Horizontal

Direct Vent (sealed combustion) with both the vent pipe and

air intake pipe terminating horizontally (through a sidewall)

with individual penetrations for the vent and air intake piping

and terminals.

No

See Table 2

D.

2. Separate

Vertical

Direct Vent (sealed combustion) with both the vent pipe and

air intake pipe terminating vertically (through the roof) with

individual penetrations for the vent and air intake piping and

terminals.

No

See Table 2

E.

3. Combination

Horizontal

Direct Vent (sealed combustion) with the vent pipe and air

intake pipe joining at a common terminal and terminating

horizontally (through a sidewall up to 15” thick) with only

one penetration.

Yes

3 - 6 Section

(61106012)

F.

4. Combination

Vertical

Direct Vent (sealed combustion) with the vent pipe and air

intake pipe joining at a common terminal and terminating

vertically (through the roof) with only one penetration.

Yes

3 - 4 Section

(100222-01)

5 - 6 Section

(100223-01)

G.

5. Indoor Air

Power Vent - Air used for combustion is provided from within

the building.

No

-----

H.

6. Optional

Separate

Horizontal

Direct Vent (sealed combustion) with both the vent pipe and

air intake pipe terminating horizontally (through a sidewall)

with individual penetrations for the vent and air intake piping

and terminals.

No

See Table 2

I.