5

VI. Electrical

A.

General. Install wiring and electrically ground boiler

in accordance with authority having jurisdiction or, in

the absence of such requirements, follow the National

Electrical Code, NFPA 70, and/or CSA C22.1 Electrical
Code.

B.

A separate electrical circuit must be run from

the main electrical service with an over-current

device/disconnect in the circuit. A service switch is

recommended and may be required by some local

jurisdictions. Install the service switch in the line

voltage “Hot” leg of the power supply. Locate the

service switch such that the boiler can be shut-off

without exposing personnel to danger in the event of

an emergency. Connect the main power supply and

ground to the three (3) boiler wires (black, white and

green) located in the junction box at the inside top of

the boiler jacket. If a low water cutoff is to be used,

connect the low water cutoff so that all 120V power

to boiler is interrupted if the low water cutoff’s switch

opens.

C.

Refer to Figures 28 and 29 for details on the internal

boiler wiring.

DANGER

Positively assure all electrical connections are unpowered before attempting installation or service of

electrical components or connections of the boiler or building. lock out all electrical boxes with padlock

once power is turned off.

WARNING

Failure to properly wire electrical connections to the boiler may result in serious physical harm.
Electrical power may be from more than one source. Make sure all power is off before attempting any

electrical work.
Each boiler must be protected with a properly sized over-current device.

Never jump out or make inoperative any safety or operating controls.
The wiring diagrams contained in this manual are for reference purposes only. Each boiler is shipped with

a wiring diagram attached to the front door. Refer to this diagram and the wiring diagram of any controls

used with the boiler. Read, understand and follow all wiring instructions supplied with the controls.

NOTICE

All wire, wire nuts, controls etc. are installer supplied unless otherwise noted.

NOTICE

This boiler is equipped with a high water temperature limit located inside the internal wiring of the boiler.

This limit provides boiler shutdown in the event the boiler water temperature exceeds the set point of the

limit control. Certain Local Codes require an additional water temperature limit. In addition, certain types

of systems may operate at temperatures below the minimum set point of the limit contained in the boiler.
If this occurs, install an additional water temperature limit (Honeywell L4006 Aquastat) located in the system

piping as shown in the Water Piping and Trim Section of this manual. Wire as indicated in the Electrical

Section of this manual.