9

I.

Sequence of Operation. See Figure 39. If boiler fails

to operate properly, see Troubleshooting Tree in Section

IX: Service.

J.

Check pilot burner flame. See Figure 41. Flame

should be steady, medium hard blue enveloping 3/8 to

½ inch of sensing probe.

K.

Check main burner flame. See Figures 40. Flame

should have clearly defined inner cone with no yellow

Figure 40: 1 Inch Main Burner flame

Figure 41: Pilot Burner Flame

Figure 39: Sequence of Operation

tipping. Orange-yellow streaks should not be confused

with true yellow tipping.

L

. Check thermostat operation. Raise and lower

temperature setting to start and stop boiler operation.

M.

Check ignition control module shut-off. Disconnect

pilot lead wires from gas valve. If burners do not

shutdown, determine cause of malfunction. Replace

necessary items and check operation.

N.

Check low water cutoff (if so equipped).

1. Adjust thermostat to highest setting.
2. With boiler operating, open drain valve and slowly

drain boiler.

3. Main burners and pilot burner will extinguish and

blower will stop when water level drops below low

water cutoff probe. Verify limit, thermostat or other

controls have not shut off boiler.

4. Adjust thermostat to lowest setting. Refill boiler.