IX. Service

A.

General. Inspection and service should be conducted

annually. Turn off electrical power and gas supply while

conducting service or maintenance. Follow instructions

TO TURN OFF GAS TO APPLIANCE. See Figure 36.

B.

Low water cutoff (if so equipped).

Probe Type (Annual Service). Probe type LWCO

should be removed once a year, examined and

cleaned of any dirt accumulations to assure proper

operations. Do not attempt to repair mechanisms in the

field. Complete replacement mechanisms, including

necessary gaskets and installation instructions, are

available from the manufacturer.

C.

Vent/Air Intake System. Inspect for obstructions, soot

accumulation, proper support, and deterioration of pipe,

fittings, and joints.
1. Clean terminal screens. Terminals must be free of

obstruction, undamaged, with screens securely in

place.

2. Terminal and wall thimbles (if used) must be

weathertight.

3. Pipe must be full round shape, and show no damage

from impact or excessive temperature.

4. Pipe must be supported at minimum five (5) foot

intervals and must not sag.

5. All vent joints must be secure and watertight.
6. All air intake joints must be secure and airtight.

Horizontal vent tee drain or vertical vent tee drain

(if used) must have minimum 6 inch trap and allow

condensate to flow freely. To Clean:
a. Disconnect drain tube from drain fitting.
b. Flush drain tube with water. Fill trap with water.
c. Securely fasten drain tube to drain fitting,

providing gas-tight and watertight seal.

7. If pipe must be disassembled for removal of

obstructions or resealing of joint, see Section III,

Paragraph C.

D.

Boiler Flue Passages. Inspect for blockage or soot

accumulation.
1. Remove Main Burners. See Figure 44.

a. Remove front door.
b. Remove air intake box front door.

i. Remove sheet metal screws.

c. Disconnect pilot tubing and pilot lead wires at

the gas valve.

DANGER

This boiler uses flammable gas, high voltage electricity, moving parts, and very hot water under high

pressure. Assure that all gas and electric power supplies are off and that the water temperature is cool

before attempting any disassembly or service.

Assure that all gas valves and electrical disconnect switches are off before attempting any disassembly

or service.
Do not attempt any service work if gas is present in the air in the vicinity of the boiler. Never modify,

remove or tamper with any control device.

WARNING

This boiler must only be serviced and repaired by skilled and experienced service technicians.
If any controls are replaced, they must be replaced with identical models.
Read, understand and follow all the instructions and warnings contained in all the sections of this

manual.
If any electrical wires are disconnected during service, clearly label the wires and assure that the wires

are reconnected properly.
Never jump out or bypass any safety or operating control or component of this boiler.
Read, understand and follow all the instructions and warnings contained in All of the component

instruction manuals.
Assure that all safety and operating controls and components are operating properly before placing

the boiler back in service.