beautypg.com

Burnham SCG 1100-H4 User Manual

Page 32

background image

9. Air Intake Connections for Direct Vent and Sealed

Combustion Appliances*:

The Air Intake Tee may be used on approved direct vent

and sealed combustion appliances that have separate (non-

concentric) air intake and flue exhaust collars. The male end

of the tee connects to EZ Seal appliance adapters and the tee

takeoff/snout connects to the appliance air intake.

• Insert the male end of the Air Intake Tee into the female

end of the EZ Seal vent section or appliance adapter and

complete the ring and tab connection.

• Insert the male end of the next SC section into the

female end of the Air Intake Tee and secure as described

elsewhere in this manual.

• Connect the tee takeoff to the appliance combustion air

inlet using appropriate hose or pipe.

* Direct Vent Appliances are constructed and installed so that

all air for combustion is supplied directly from the outside

atmosphere. The passage for the combustion air is allowed

a small amount of leakage in the building environment. No

special installation considerations are required to use Saf-T

Vent SC on Direct Vent appliances unless specified by the

appliance manufacturer. Sealed Combustion appliances are

similar to Direct Vent except the combustion air passage must

be sealed to prevent leakage within the building envelope.

When Saf-T Vent SC is used on approved Sealed Combustion

appliances the joints of the outer jacket must be sealed with

a foil tape (example: 3M 425), or approved silicone sealant

(example: Dow Corning 732).

10. Condensate Drains:

When An Internal Condensate Drain is NOT Part of the

Appliance:

• A Saf-T Vent SC In-Line Drain Section is strongly

recommended. Install this drain fitting as close to the

appliance flue collar as possible.

• A condensate drain is required for every 30 feet of

horizontal vent and at/near the bottom of a vertical stack.

• Use the In-Line Drain Section for a straight horizontal or

vertical run. When used horizontally, rotate the fitting so that

the drain tube is as vertical as possible.

• A Condensate Drain Tube Kit is available to direct the condensate

to an appropriate location, i.e. floor drain or vented sanitary

sewer connection. A trap loop must be formed into the drain

hose and must be a diameter that is at least four (4) times the

appliance’s rated stack pressure in inches of water column or 3

inches, whichever is greater. Secure the loop with a cable tie.

Prior to final assembly the trap loop must be ‘primed’ by pouring

a small quantity of water into the drain hose. Inspect at least

annually to verify the trap is ‘primed’.

• Follow all local and national codes and regulations for the

draining of acidic condensate.

• In cold climates do not install a condensate drain on the exterior

of the building. Doing so may result in dangerous icy conditions

on surfaces near the drain and may cause damage to the vent

system and/or the building exterior.