L-force loader – Lenze Loader L-force Loader User Manual
Page 31
L
DMS 4.0 EN - 07/2007
31
L-force Loader
Control via script files
Structure of the script file
Target system-dependent settings - [DEVICE...] sections
Every target system must have a [DEVICE???] section. The question marks must be replaced
by consecutive numbers (001 ... NumberOfDevices).
r
If you have defined the key NumberOfDevices=3 in the [COMMON] section, the
following three sections must be available:
[DEVICE001], [DEVICE002], [DEVICE003].
r
The target systems are processed subsequently, starting with [DEVICE001].
The following settings can be made for every section:
Key
Parameter
NodeAddress
Designation of the bus server and address of the target system (see following
examples).
• The address is displayed in the dialog area in the Busserver field.
Example 1 - communication via system bus
• In the following example, the target system has the CAN node address "11".
• Check also key "SDO"!
NodeAdress=Lenze OPC Systembus Server.11
Example 2 - communication via LECOM
• In the following example, the target system has the LECOM node address "5".
NodeAdress=Lenze OPC Lecom Server.1-5
Example 3 - communication with L-force 9400 Servo Drives via diagnostic adapter
If only one diagnostic adapter is connected to the PC, the default address "0" is to be
indicated:
NodeAdress=Lenze OPC Diagnostics Server.0
If several diagnostic adapters are connected to the PC, unambiguous addressing
requires the indication of the diagnostic adapter's serial number.
• The serial number (S/N) is printed on the diagnostic adapter.
• The serial number can also be displayed in the diagnostics configurator. For this
purpose, select the diagnostic adapter in the configurator and click Diagnostics
on the Common tab.
• In the following example, the diagnostic adapter has the serial number
"00001628".
NodeAdress=Lenze OPC Diagnostics Server.1-1628
Example 4 - communication with 9400 Servo Drives via Ethernet NRT
• In the following example, the OPC Ethernet server has the default address "1".
• The IP address is specified with the "IP" key.
NodeAddress=Lenze OPC Ethernet Server.1
IP
IP address
• Only required for communication with 9400 Servo Drives via Ethernet NRT.
• The dots of the IP address must be replaced by underline characters.
Example:
IP=172_31_201_38
SDO
Parameter channel (1 or 2) for communication.
• Only required for communication via system bus (CAN).
• For a better performance, select the same parameter channel for all devices in the
script file.
• If "0" is set, there is no division into channels and the entire node address range
is accepted.