C14010 | encoder type dfin, C14011 | no. of increments dfin, C14012 | signal format dfin – Lenze E94AYFLF Digital frequency module User Manual
Page 39: C14013 | initialisation time dfin, C14014 | track monitoring dfin, C14010, C14011, C14012, C14013, C14014
EDS94AYFLF EN 3.2 - 10/2010
L
39
Digital frequency extension module | Parameter setting & configuration
Parameter reference
Parameter list | C14010
C14010
C14011
C14012
C14013
C14014
Parameter | Name:
C14010 | Encoder type DFIN
Data type: UNSIGNED_8
Index: 10565
d
= 2945
h
Digital frequency extension module in module receptacle MXI2:
Selection of the encoder type for digital frequency input X9
Selection list
(Lenze setting in bold)
1 Digital frequency output DFOUT
2 TTL encoder
;
Read access ; Write access CINH PLC-STOP No transfer
Parameter | Name:
C14011 | No. of increments DFIN
Data type: UNSIGNED_32
Index: 10564
d
= 2944
h
Digital frequency extension module in module receptacle MXI2:
Number of increments for digital frequency input X9
• Definition of the number of pulses for one "mechanical" revolution.
Setting range
(min. value | unit | max. value)
Lenze setting
1
16384 2048
;
Read access ; Write access CINH PLC-STOP No transfer
Parameter | Name:
C14012 | Signal format DFIN
Data type: UNSIGNED_8
Index: 10563
d
= 2943
h
Digital frequency extension module in module receptacle MXI2:
Signal form for digital frequency input X9
• Selection of how to interpret the input signal.
Selection list
(Lenze setting in bold)
0 4x evaluation (A, B)
1 A:Increments B:Sign
2 Increments A:pos. B:neg.
;
Read access ; Write access CINH PLC-STOP No transfer
Parameter | Name:
C14013 | Initialisation time DFIN
Data type: UNSIGNED_16
Index: 10562
d
= 2942
h
Digital frequency extension module in module receptacle MXI2:
Initialisation time for digital frequency input X9
• Waiting time after which the "Enable" signal is evaluated and the track monitoring modes are switched active.
Setting range
(min. value | unit | max. value)
Lenze setting
0
ms
65535 3000 ms
;
Read access ; Write access CINH PLC-STOP No transfer
Parameter | Name:
C14014 | Track monitoring DFIN
Data type: UNSIGNED_8
Index: 10561
d
= 2941
h
Digital frequency extension module in module receptacle MXI2:
Monitoring configuration for digital frequency input X9
• Selection when track monitoring modes (open circuit detection) are active.
Selection list
(Lenze setting in bold)
1 Active after initialisation time
2 Active after enable signal
;
Read access ; Write access CINH PLC-STOP No transfer