Digital frequency extension module | Parameter setting & configuration
Digital frequency input
Parameter setting
Monitoring of the "Enable" or "Lamp control" signal
If the +5 V encoder voltage is not controlled by the digital frequency extension module, a
digital signal can be read in and monitored via pin 8 of the digital frequency input X9, e.g.
the "Lamp control" signal of an encoder or the "Enable" signal of an upstream digital
frequency module.
If pin 8 of the digital frequency input X9 is not set to HIGH level (+5V) after the
initialisation time has elapsed, a fault message is generated and the response set in
The binary status of pin 8 is also displayed at the output DFIN_bSense of the system
block LS_DigitalFrequencyInput .
Track monitoring (open circuit detection)
The signal tracks A, B, and Z are monitored with regard to their differential voltage value.
For the activation of track monitoring, two modes are available in
Monitoring is both done at standstill and while the encoder is rotating.
If track monitoring responds, a fault message is generated and the response set in
– At the same time the corresponding output DFIN_bTrackAError, DFIN_bTrackBError
or DFIN_bTrackZError of the system block LS_DigitalFrequencyInput is set to TRUE.
C13014 / C14014 = "1"
C13014 / C14014 = "2"
The track monitoring modes are activated after the
initialisation time has elapsed.
• The initialisation time is set in
The track monitoring modes only become active if pin 8
of the digital frequency input X9 is set to HIGH level
(+5 V).
• They may be activated e.g. by an encoder (status
"Lamp control") or an upstream digital frequency
module (status "Enable").
• When this mode is selected, monitoring can be
switched active by a signal source if the levels on the
tracks have valid values.