beautypg.com

Lenze I/O system 1000 User Manual

Page 26

background image

4

Mapping the real station structure in the »PLC Designer«

4.4

Configuring I/O modules on the CANopen bus coupler module

26

Lenze · I/O system 1000 · commissioning guidelines for the PLC Designer · DMS 1.2 EN · 11/2012 · TD05

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

4.4.1

Special features of the CANopen bus coupler module (EPM-S110)

When the counter modules (EPM-S600 ... S604) at the CANopen bus coupler module (EPM-S110) are

used, the following sequence has to be complied with during configuration.

How to configure the EPM-S600 ... S604 counter modules:

1. Add CANopen bus coupler module (EPM-S110) to the device view.
2. Add I/O discs and counter discs.
3. Click the "EPM_S110" device in the device view S110to open its settings.
4. On the CANopen Remote Device tab:

Activate the Expert settings option.

Deactivate the Autoconfig. PDO Mapping option.

5. Execute the menu command WindowClose All Editors.

Note!

Before inserting I/O compound modules below a CANopen bus coupler module (EPM-

S110) in the »PLC Designer«, close the tab to the EPM-S110.

• When inserting I/O compound modules while the tab is open, no I/O image is

displayed for the modules.

• When all I/O compound module are inserted, the tab to the EPM-S110 can be opened

again.