beautypg.com

3 establish communication, Establish communication, 3establish communication – Lenze I/O system 1000 User Manual

Page 12

background image

3

Establish communication

3.1

Establishing communication with the L-force Controller

12

Lenze · I/O system 1000 · commissioning guidelines for the PLC Designer · DMS 1.2 EN · 11/2012 · TD05

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

3

Establish communication

This chapter describes how to establish a communication between the Engineering PC with the

installed »PLC Designer« and the I/O system 1000.

3.1

Establishing communication with the L-force Controller

• Connect the Engineering PC with the L-force Controller via a network cable, as the »PLC

Designer« accesses the L-force Controller via Ethernet.

• Make the IP settings with the »PLC Designer«.

How to check the communication settings:

1. Double-click the L-force Controller in the Device view to open the settings and properties of

the device in the Editor view.

2. Make the desired settings on the Communication settings tab.

• Click the Add gateway button to insert a gateway.
• Enter the desired IP address of the L-force Controller.

3. Click OK to add the L-force Controller as gateway.

The system manual for the I/O system 1000 contains detailed information on the

communication via the respective fieldbus (CANopen, EtherCAT, ...).

Note!

Please observe the following predefined IP addresses when commissioning your IPC for

the first time:

• Engineering PC: 192.168.5.100
• L-force Controller: 192.168.5.99