12 Error messages

2014-06-12

44

12 Error

messages

Error display (code)

Cause

Remedy

The total number of relay switching
operations has been reached.

h

Increase the total number of relay switching
operations

v

Chapter 7.11 “C 120 Limit value for relay

switching operations”

h

Acknowledge with the Reset key

v

Chapter 7.12 “C 121 Count for relay switching

operations”

0002

Terminal temperature
is outside the -10 to 80°C range

h

Check the ambient temperature

h

Acknowledge with the Reset key

If that does not help, send the instrument in

0003

Reference voltage
The measured value is above 999 or below
-999 and is thus outside the 3-digit display
range.

-

A/D converter error

h

Acknowledge with the Reset key

If that does not help, send the instrument in

0004

Calibration constant

The instrument must be returned to JUMO for repair.

h

Send the instrument in

v

Chapter 2.1 “Service addresses”

0005

Configuration data
Value cannot be displayed (too large or too
small)

0006

reserved

-

0007

reserved

-