7 Configuration level

27

2014-06-12

7.8

C118 Display switch-off after timeout

7.9

C119 Warning alarm function

The warning alarm is indicated via LED KV and is output simultaneously at the binary output. The switching action can be
configured as an absolute value or as an interval to the limit value (relative).

k

Factory setting

Display switch off

Comment

0

inactive

Display is permanently switched on.

1

active

Display switches off after a timeout and re-appears,
as soon as a key is pressed.

Warning alarm function

Comment

0

inactive

Warning alarm and LED KV switched off.

1

absolute value

Warning alarm limit fixed.

2

Interval from the limit value

The warning alarm limit varies with the value of the limit set for switching
off the relay.