8 Faults

The thyristor power unit does not require any maintenance.
In the event of a fault, the following points should be observed:

8.1 Fault-finding

If faults occur during commissioning, we recommend that you first check the
positions of the internal switches.

v Section 6.3 “Summary of possible settings”

If the fault persists, check the following items:

- Is the supply voltage present for the thyristor power unit?

Check the phase sequence as well.

- Are all other connections also correct?

- Is the controller operating properly?

Check the operation manually, by using an external potentiometer.

v Section 6.4 “Control inputs”

8.2 Replacing the semiconductor fuse

If the red LED “fuse” lights up, this means that a semiconductor fuse has
blown.

h Disconnect the system from the supply voltage.
v Section 6.1 “Opening the housing”

8.2.1 Type TYA-110/3, 025 to 100, ...

Wrench 10 mm a/f