2 Operating modes

14

Power units 02.06

2.2 Burst-firing operation, for resistive loads

In this mode of operation, the power is regulated by changing the number of
full-wave cycles of the supply line voltage which are switched on during each
control period. This method is used for purely resistive loads which have a
cold resistance that is roughly the same as the hot resistance.
Since switching only takes place at the zero-crossing points, this mode of
operation produces very little RF-interference.

The internal switch S20 can be used to adjust the duty cycle to suit the system
being controlled.

v Section 6.2 “Adjustment switches S1 — 21 and pin headers X503 / X504”

Cycle time

S 20

Variable cycle time
The control unit uses the shortest available cycle time
(for fast control loops)

1

Fixed cycle time (

≈ 500ms)

Used for transformer loads, slow control loops

2