6 Settings

Controller with
voltage output

This only uses the voltage input of the thyristor power unit. A 5 k

Ω potention-

meter is required on Terminals 3 and 5 for manual operation.

6.5 Subsidiary control loops

Subsidiary control loops are primarily used to eliminate or compensate exter-
nal disturbances, such as supply-line fluctuations and changes in resistance
which would have a negative effect on the regulation. A subsidiary V

2

control

loop is set up ex-factory. With extra code TR or TO this can be changed to P
or I

2

control. The free-running economy circuit must operate with a P control

loop.

v Section 6.2 “Adjustment switches S1 — 21 and pin headers X503 / X504”

v Section 6.7 “Load current adaptation (only with extra code TR/T0)”

Switch

S

c

Automatic operation

position 1

Manual operation

position 2

H

With P or I

2

control loops (extra code TR/TO) a load current adap-

tation must be made for operating currents that are less than half
the rated load current.

Control
type

Internal switches

Application

S4

S5

S6

V

2

1

0

0

- positive TC,

- R

≈ constant

- brightness controls