6 Settings

46

Power units 02.06

6.6 Actual (power) output

The factory setting is that the actual (power) signal output corresponds to the

V

2

signal at the output of the power unit, and is therefore proportional to the

power in the load (R = constant). With the extra code TR/TO it can be switched

over to a P or I

2

signal.

v Section 6.3 “Summary of possible settings”

Adjust output

The signal at the actual (power) output is a voltage in the range 0 — 10V (cor-
responding to 0 — 100% of the particular measurement range). The trimmer
(8) “output adjust” can be used to adjust the range end value:

v Section 6.7 “Load current adaptation (only with extra code TR/T0)”

P

0

1

0

- temperature-dependent TC

- free-running economy circuit

I

2

0

0

1

- negative TC

Actual (power) signal output

Internal switches

S7

S8

S9

V

2

1

0

0

P

0

1

0

I

2

0

0

1

Action

Response

Turn trimmer fully clockwise (right)

Measurement range 0 — 100 %
corresponds to a signal 0 — 10V

Turn trimmer fully counter-clockwise
(left)

Measurement range 0 — 100 %
corresponds to a signal 0 — 5V

H

With P or I

2

control loops, a load current adaptation must be made

for operating currents that are less than half the rated load current!