3 Installation

above the unit. The thyristor power unit has enclosure protection IP00, and so
it must be mounted in such a way that bodily contact is prevented (built-in
unit).

Incorrect use

- The unit is not suitable for installation in areas with an explosion hazard

(Ex areas).

- The installation site should be free from vibration, dust, and corrosive

media.

Ambient
conditions

- Side-by-side mounting of units is permitted

- Relative humidity

Յ 75 %, no condensation

- Ambient temperature range: 0 to 45 °C

Storage temperature range: -10 to 70 °C

3.4 Wall mounting

h Fix the aluminium mounting plate to the heatsink, using the cheese-head

screws provided.

h Fix the thyristor power unit with its mounting plate to the wall, using four

screws.

3.4.1 TYA-110/3, 025..100

V

The heatsink can become very hot in operation!