Logic control inputs, Controller with current output, 6 settings – JUMO 709040 TYA-110 thyristor power unit Operating Manual User Manual

Page 44

background image

6 Settings

44

Power units 02.06

Logic control
inputs

The thyristor power unit can also be operated by the following logical signals
(e.g. two-state/single-setpoint controller outputs):
(switching pulse bursts on or off):

- current signal 0/20mA (Terminals 1, 2)

- voltage signal 0/10V (Terminals 3, 4)

- floating contact (Terminals 4, 5)

6.4.1 Combinations of external potentiometer and electronic controller

Controller with
current output

The voltage input (Terminals 3, 4) can be used together with the internal 10 V
source and a 5 k

Ω potentiometer to provide manual setting.

Switch

S

a

S

b

Automatic

open

open

Manual closed

closed

H

To prevent unintended overdriving on the changeover to manual
operation, S

a

should be mechanically coupled to S

b

. Otherwise the

two signal sources will be added together for a moment.